62 RMWH-SVX001C-EN
Appendix E: BACnet Objects
TruSense RMWH Refrigerant
Monitor—BACnet
Section Object Name Channel # Object Type Inst # Property Notes
General
Product ID
General
Analog Input 1 Read “CG”
Firmware Version Analog Input 2 Read
Build(MSB:2b)/Major(1b)/Minor(1b)
Reserved 4 Analog Input 4 Read 0
Reserved 5 Analog Input 5 Read
0
Reserved 6 Analog Input 6 Read 0
Unit Status Analog Input 7 Read Refer to “Unit Status Flags,” p. 64
ACK button Analog Input 8 Write ACK by writing 1 to it
RESET button Analog Input 9 Write Refer to “RESET Button Actions,” p. 64
Channels
1 Gas Number
Channel
1
Analog Input 10 Read Refer to “Gas Types,” p. 65
1 Gas Conc. Analog Input 11 Read
ppm
1 Status Analog Input 12 Read Refer to “Channel Status Flags,” p. 65
1 Reserved Analog Input 13 Read 0
2 Gas Number
Channel
2
Analog Input 14 Read Refer to “Gas Types,” p. 65
2 Gas Conc. Analog Input 15 Read
ppm
2 Status Analog Input 16 Read Refer to “Channel Status Flags,” p. 65
2 Reserved Analog Input 17 Read 0
3 Gas Number
Channel
3
Analog Input 18 Read Refer to “Gas Types,” p. 65
3 Gas Conc. Analog Input 19 Read
ppm
3 Status Analog Input 20 Read Refer to “Channel Status Flags,” p. 65
3 Reserved Analog Input 21 Read 0
4 Gas Number
Channel
4
Analog Input 22 Read Refer to “Gas Types,” p. 65
4 Gas Conc. Analog Input 23 Read
ppm
4 Status Analog Input 24 Read Refer to “Channel Status Flags,” p. 65
4 Reserved Analog Input 25 Read 0
5 Gas Number
Channel
5
Analog Input 26 Read Refer to “Gas Types,” p. 65
5 Gas Conc. Analog Input 27 Read
ppm
5 Status Analog Input 28 Read Refer to “Channel Status Flags,” p. 65
5 Reserved Analog Input 29 Read 0
6 Gas Number
Channel
6
Analog Input 30 Read Refer to “Gas Types,” p. 65
6 Gas Conc. Analog Input 31 Read
ppm
6 Status Analog Input 32 Read Refer to “Channel Status Flags,” p. 65
6 Reserved Analog Input 33 Read 0
7 Gas Number
Channel
7
Analog Input 34 Read Refer to “Gas Types,” p. 65
7 Gas Conc. Analog Input 35 Read
ppm
7 Status Analog Input 36 Read Refer to “Channel Status Flags,” p. 65
7 Reserved Analog Input 37 Read 0
8 Gas Number
Channel
8
Analog Input 38 Read Refer to “Gas Types,” p. 65
8 Gas Conc. Analog Input 39 Read
ppm
8 Status Analog Input 40 Read Refer to “Channel Status Flags,” p. 65
8 Reserved Analog Input 41 Read 0
9 Gas Number
Channel
9
Analog Input 42 Read Refer to “Gas Types,” p. 65
9 Gas Conc. Analog Input 43 Read
ppm
9 Status Analog Input 44 Read Refer to “Channel Status Flags,” p. 65
9 Reserved Analog Input 45 Read 0