Document No: LT0119 F3200 Operator's Manual
Network Systems
Issue 2.04 29 July 2002 Page 11-11
11.6.3 NETWORK PANEL STATUS
Pages 0, 1, and 2 show a list of fault conditions with up to 6 fault conditions per page as
follows:
Network Panel Status Page 0
ScanF - The Local Panel is not receiving any data from the Remote Panel.
LnkIA - The Local Panel is not receiving Channel A test data from the Remote
Panel.
LnkIB - The Local Panel is not receiving Channel B test data from the Remote
Panel.
SysFlt - The Remote Panel has a system fault.
NetFlt - The Remote Panel has a network fault.
Stdby - The Remote Panel has generated a standby condition.
Network Panel Status Page 1
Abnml - The Remote Panel has an Abnormal status present.
BellI - The Remote Panel's bells are isolated.
TEvac - The Remote Panel is asserting Trial Evacuation.
SilAlm - The Remote Panel is asserting Silence Alarms (Silence Bells)
BrigT - The Remote Panel is asserting Brigade Test.
SysFRcl - The Remote Panel has information that should be recalled on its own LCD
display using the System Fault recall command.
Network Panel Status Page 2
MafAlm - The panel has a MAF alarm condition.
MafFlt - The panel has a MAF fault condition.
MafIso - The panel has a MAF isolation condition.
NMAlm - The panel has a non-MAF alarm condition.
NMFlt - The panel has a non-MAF fault condition.
NMIso - The panel has a non-MAF isolate condition.
Network Panel Status Page 3
CmnPtI - Common point isolate
SysTst - A system/auto-test is in progress.
Tst Fl
I
- Test fail indication. A zone/system/auto-test has failed and the test fail
buzzer is currently active.
PSUFlt - Indicates a Power Supply or battery fault e.g. mains fail, charger low,
battery low, battery connection or battery capacity.
LatBVLO - For New Zealand mode, this indicates a latched Battery Very Low Alarm.
BSR - For New Zealand mode, indicates Building Services Restore keyswitch
activated.
Network Panel Status Page 4
Page 4 shows the 4 totals being transmitted onto the network by the panel - alarm, fault,
isolate, other. For the local panel the page 4 totals only show the off normal conditions
being generated by this panel - these may not be the same as the values shown on the
base display because the base display may show combined totals from multiple panels.