Document No: LT0119 F3200 Operator's Manual
Network Systems
Issue 2.04 29 July 2002 Page 11-15
11.8.3 NETWORK SYSTEM FAULTS RESET
To send a system fault reset command to a remote device from the base display, press:
Then enter the SID number 1 to 254 using the numeric keys 0 to 9, followed by the
ENTER key.
The top line of the display then shows the name of the selected SID and the bottom line
gives options 1 to 3 as follows:
1:System Test, 2:Faults Reset, 3:Bells
Select option 2: Faults Reset, i.e. press numeric key 2.
When an F3200 or NDU receives a network system fault reset command the buzzer will
be silenced.
11.8.4 NETWORK RECALL DATABASE CRCs
It is possible to recall the database CRC from a remote F3200 or NDU.
This information can be used as part of an AS1851.8 testing schedule.
From the base display, press:
then select either:
1. For all panels (SIDs).
2. Local panel.
3. A selected panel.
For Option 1, the LCD will first display the database CRC for the local panel. The NEXT
and PREV keys may then be used to step to the next or previous panel in the system.
Some devices on the network may not support the remote database CRC recall function,
in which case an error message will be displayed and an option given to retry (ACK key)
or to step to the next panel (NEXT key).
To exit from the recall at any time, press the CLEAR key.
NOTE: Any changes made to the database will change the numbers displayed in
this recall. Thus, if the database is changed, the new numbers should be
recorded in the log book and the service company advised.