Document No: LT0119 F3200 Operator's Manual
Appendix A
Issue 2.04 29 July 2002 Page A-3
ACTUATING DEVICE COMPATIBILITY NOTES
1) The maximum number of detectors per AZC allowed by the standard is 40.
2) Those detectors shown in brackets have the same characteristics as the
current models.
3) Detectors indicated by a "x" may be used in INTRINSICALLY SAFE AREAS in
conjunction with approved and compatible, intrinsically safe adaptors. The
number allowed in a particular circuit may be less than the maximum shown.
Refer to the Installation Manual for details.
V41/42/44B detectors have flameproof enclosures.
4) Detectors indicated by a "+", which are used in HOSTILE CLIMATIC
ENVIRONMENTS, may be directly connected to the panel, if they are not
required to be intrinsically safe.
5) Detectors indicated by a "*", are not current models and should not be used for
new installations.
6) Detectors indicated by an "&", normally use an incandescent lamp which will
have a low intensity when used in mode 1.
The lamp can be replaced with an LED kit - contact supplier.
7) The B111B beam and V41B/V42B/V44B flame detectors require power from
the fused +24 VDC supply.
8) Hard Contact devices are indicated by a #. Where an AZC has only hard
contact devices circuit resistance must be less than 150 Ohms (i.e. reduce line
voltage to less than 2.5V), to distinguish instant alarms (B1) from alarms (B2)
(e.g. to override AVF).
9) The Intertec detectors require a series diode to be fitted for compatibility.
Consult manufacturer for detail.
10) The Olsen FW81B code for fire wire has been replaced by FW followed by the
temperature rating in °C, eg. FW68, FW105. Only FW68 is currently approved
and listed.