Document No: LT0119 F3200 Operator's Manual
System Specifications
Issue 2.04 29 July 2002 Page 3-7
3.3.4 FUSES
Location : MAF/PSU PCB
Number
Name Size Rating Type
F1 +VBF1 5 x 20mm 2A Glass Cartridge, Std
F2 +VBF2 5 x 20mm 6A Glass Cartridge, Std
F3 +VNBF 5 x 20mm 2A Glass Cartridge, Std
F4 +VE 5 x 20mm 2A Glass Cartridge, Std
F5 Mains In 5 x 20mm 6A Glass Cartridge, Std
F7 +VBELLS 5 x 20mm 2A Glass Cartridge, Std
3.3.5 QUIESCENT & ALARM CURRENTS
At 24Vdc battery supply, nominal currents:
Quiescent
Alarm (2 Zone)
FP0550, FP0551 (notes 1 & 2) 130mA 275mA
8 Zone Module
- all AZCs disabled 4mA
- all AZCs enabled (notes 2-6) 82mA 97mA
Current per enabled AZC (note 3) 10mA
8 Relay Module
- all supervision disabled 4mA
- all supervision enabled 6mA
Current per relay on 11mA
Notes
1. FP0550 and FP0551 includes Controller/Display, MAF/PSU and 1 x 8ZM with all
AZCs enabled and with EOLRs (2K7 for mode 1 or 2).
2. Quiescent current for enabled AZC is for modes 1 or 2 (standard or high current)
and includes the 2K7 EOL, but not the detector current (up to 4mA detector
current per AZC).
3. The alarm current shown is for mode 1. Refer to the Technical or Installation
manual for detail on other modes.
4. The 8 Zone Modules are supplied from the fused battery supply (+VE) via the
22V regulator which has a maximum rating of 800mA.
5. The 8 Relay Modules are supplied from the fused battery supply.
6. Quiescent and alarm currents do not include external loads e.g. door holders,
bells, etc.