F3200 Operator's Manual Document No: LT0119
General Display & Keypad Operation
Page 4-6 29 July 2002 Issue 2.04
4.2.3 SELECTIVE FUNCTIONS
From the base display, the following functions can be selected:
System Functions
Menus for system functions can be selected by pressing "RECALL", "SYSTEM", "SET",
"TEST" or "PRINT".
Direct acting (non-menu) functions include "BELLS ISOL", "BATT TEST" and "BRIG
TEST".
Refer to Chapter 6.
Zone Functions
Zone functions can be selected directly by pressing "ZONE", or indirectly by pressing
"RESET", "ISOL", "TEST", "ALARM TEST" or "FAULT TEST".
Refer to Chapter 7.
Relay Functions
Relay functions can be selected directly by pressing "RELAY", or indirectly by pressing
"RESET", "ISOL" or "TEST".
Refer to Chapter 8.
4.2.4 ZONE NUMBERING
An F3200 panel maps as follows a variety of inputs and output to zones so that they may
be accessed and controlled over a network.
Zones 1-64 - Alarm zones 1-64
Zones 65-128 - Module relays 1-64
Zones 129-192 - Open collectors 1-64
Zone 193 - Bells
Zone 194 - Ancillary relay 1
Zone 195 - Ancillary relay 2
Zone 196 - Ancillary relay 3 (if not bells)
Zone 197 - Plant isolate
When the status of a relay or open collector is being shown on the LCD, the display
shows both the zone number and the relay or open collector number. This mapping
scheme means that there are often two ways of doing the same thing.
For example, to display the status of module relay 1 it is possible to use either the ZONE
key (and select zone 65) or the RELAY key (and select module relay 1).