Document No: LT0119 F3200 Operator's Manual
Operating Instructions - Brigade Functions
Issue 2.04 29 July 2002 Page 5-3
5.1.2 FFCIF MODE 3 OPERATION
When the FIP is displaying an alarm the LCD display includes the following information:
(i) The time at which the alarm occurred.
(ii) The zone alarm type.
(iii) Whether the alarm is acknowledged or not (Figure 5.1 shows an unacknowledged
alarm).
(iv) The total number of alarms and the sequence number of the currently displayed
alarm.
(v) The zone number and location.
(vi) For network systems the AND/. key may be used to display additional
information.
The F3200 FIP maintains a list of alarms in the order in which they occurred. In the
absence of operator intervention, the LCD display will show the first alarm. All alarms in
the list can be viewed, one by one, by pressing the "NEXT" or "PREV" keys.
Each alarm can be individually acknowledged when it is displayed by pressing the "ACK"
key. The text "ACKD" appears on the display whenever an acknowledged alarm is
viewed.
Once an alarm has been acknowledged, it can be removed from the alarms list by:
(i) Pressing the "RESET" key - all acknowledged alarms are RESET, and removed
from the list; or
(ii) Pressing the "ISOLATE" key - all acknowledged alarms are ISOLATED, and
removed from the list; or
(iii) The alarm condition being cleared from a non-latching detector on a non-latching
zone.
After all alarms have been acknowledged, pressing the "CLEAR ESC" key will exit from
the FFCIF alarm list display even if there are still zones in alarm. After exiting, the FFCIF
alarm list display can be recalled by using the RECALL Alarms list command from the
base display.