F3200 Operator's Manual Document No: LT0119
Operating Instructions - Zone Functions
Page 7-6 29 July 2002 Issue 2.04
7.2.3 OPERATING SEQUENCE - ZONE RANGE
To isolate or de-isolate a range of zones from the base display, press:
The LCD will display the selected range of zones, i.e. zone n n to zone m m inclusive,
plus the options to isolate or de-isolate the range.
To isolate the range of zones, press:
To de-isolate the range of zones, press:
7.2.4 NOTES
(a) Single digit zone numbers can be entered as "n" followed by "AND" or "ISOL" as
appropriate.
(b) Isolated zone(s) will register and indicate alarm and fault but are prevented from
entering FFCIF mode or operating system outputs.
(c) If the zone is in Auto-Reset mode, the zone may still be isolated and de-isolated
but will remain in Auto-Reset mode. A zone which is in Auto-Reset mode and is
isolated will not operate the bells for 2 seconds when an alarm occurs.
(d) Any zones which are currently in alarm or fault will not be de-isolated by a zone
range command and will remain isolated but they may be de-isolated by a single
zone de-isolate command.