4 - 14 Configuration Issue 13 February 2001
Alarm Menu From the CONFIGURATION menu, select ALARM to bring up the
ALARM menu. This menu allows you to enable or disable various
alarm operations. The following shows the ALARM menu.
Set Critical alarm equals Major alarm (CR=MJ): A hardware DIP
switch (switch 6 of SW202 on the BJB board) and a software switch are
associated with this field. If this field is enabled, all the CRITICAL
alarms in the system will behave as if they are at the MAJOR severity
level. To enable this field, make sure the hardware DIP switch is ON,
and use the <+> or <-> key to set the field value as ENABLE; press
<ENTER> key to save the change. This option is useful for customer
alarm systems which recognize only major and minor alarm levels and
not the new third level, critical.
Alarm Test (Test ALA) enable/disable switch: A hardware DIP
switch (switch 5 of SW202 on the BJB board “alarm test”) and a
software switch are associated with this field. This field must be enabled
to perform an alarm test. To enable this field, make sure the hardware
DIP switch is ON, and use the <+> or <-> key to set the field value as
ENABLE; press <ENTER> key to save the change.
Test High Voltage (TEST HV) enable/disable switch: A hardware
DIP switch (switch 4 of SW202 on the BJB board) and a software switch
are associated with this field. This field must be enabled to test the High
Voltage shutdown of rectifiers during alarm test. To enable this field,
make sure the hardware DIP switch is ON, and use the <+> or <-> key
to set the field value as ENABLE; press <ENTER> key to save the
change. Enabling of this switch is not recommended with serial
rectifiers.
Alarm Cut Off for Critical alarm (ACO CR) enable/disable switch:
This field controls the Alarm Cut Off operation for the Critical severity
level alarms. This field must be enabled for the ACO button field on the
MAIN menu to have effect. To enable this field, use the <+> or <-> key
to set the field value as ENABLE; press <ENTER> key to save the
change.
ALARM
CR = MJ : EN
TEST ALM : DIS
TEST HV : DIS (S)
ACO CR : EN
ACO MJ : EN
ACO MN : EN