Tyco Electronics Galaxy SC Controller J85501F-1
4 - 16 Configuration Issue 13 February 2001
PLANT V: This setting controls the plant voltage for float and boost
modes. Move the cursor to one of the fields and use the <+> or <-> key
to adjust the voltage to the desired level. Press <ENTER> to save the
change.
I LIMIT %: This setting controls the current limit value of all serial
rectifiers as a percentage of rectifier capacity. Use the <+> or <-> key to
adjust the current limit value to the desired level. Press <ENTER> to
save the change.
For plants with a mix of serial and ferroresonant rectifiers, it is
recommended that the current limit setting for the serial rectifiers be set
at a maximum value of 100%. This will keep all serial rectifiers in the
plant at a maximum load value that is within their rated value, even if
the other rectifiers in the plant are adjusted to an output voltage that is
below the setting for the serial rectifiers in the PLANT V field of RECT
MNGR.
SHVSD: The configuration of this field sets the internal high voltage
shutdown value of all serial rectifiers for both the Float and Boost plant
modes.
Note: this value is based on rectifier output voltage and not measured
plant voltage. Move the cursor to one of the fields and use the <+> or
<-> key to adjust the voltage to the desired level. Press <ENTER> to
save the change.
VOLT STEP: The configuration of this field sets the increment of
voltage change for the voltage settings above, in increments of 0.01, 0.1
or 1.0 volts. Use the <+> or <-> key to select the desired step change
voltage increment level. Press <ENTER> to save the change.
LD SHARE: The configuration of this field enables or disables the
rectifier load share feature. Use the <+> or <-> key to toggle between
enable or disable. Press <ENTER> to save the change.
RMOVE RECT: May be used to remove a rectifier from the
configuration. Rectifier number is selected using <+> and <-> keys,
<ENTER> will remove the specified rectifier from the configuration.
Removing a rectifier will cause all associated alarms generated by the
rectifier to be filtered and ignored by the Galaxy SC.