Tyco Electronics Galaxy SC Controller J85501F-1
4 - 32 Configuration Issue 13 February 2001
a software switch associated with it. To set the field value to EN(able),
the hardware switch must be set to ON (1 position) and software switch
must be enabled; all other positions of the switches will result in a
DIS(able) mode. The four possible values are: DIS(H), DIS(H,S),
DIS(S), EN. Toggle the switch to change the hardware switch value, use
the <+>, <-> key to change the software switch value.
Enable/Disable Remote Rectifier Turn ON (REMOTE ON): This
field allows you to enable or disable the ability to turn on the rectifiers
remotely. For example, if this field is enabled, you can login through the
remote port and issue a command to turn on all the rectifiers. This field
has a hardware switch (switch 7 of SW203 on the BJH board) and a
software switch associated with it. To set the field value to EN(able), the
hardware switch must be set to ON (1 position) and software switch
must be enabled; all other positions of the switches will result in a
DIS(able) mode. The four possible values are: DIS(H), DIS(H,S),
DIS(S), EN. Toggle the switch to change the hardware switch value; use
the <+>, <-> key to change the software switch value.
Enable/Disable Remote Rectifier Turn OFF (REMOTE OFF): This
field allow the users to enable or disable the ability to turn OFF the
rectifiers remotely, for example if this field is enabled, the users who
login through the remote port can issue a command to turn OFF all the
rectifiers. This field has a hardware switch (switch 8 of SW203 on the
BJH board) and a software switch associated with it. To set the field
value to EN(able), the hardware switch must be set to ON (1 position)
and software switch must be enabled; all other positions of the switches
will result in a DIS(able) mode. The four possible values are: DIS(HW),
DIS(HW,SW), DIS(SW), EN. Toggle the switch change the hardware
switch value; use the <+>, <-> key to change the software switch value.
Configure the Rectifier Sequencing (SEQUENCE): This field allows
you to Enable or Disable the Rectifier turn-on sequencing procedure.
Use the <+>, <-> key to set the value and press <ENTER> to save the
change. Rectifier Sequencing requires that ETR and ETRR (BJT TB3
12-13) external wiring be brought to the Galaxy SC, and optionally RO
& ROR (BJT TB3 14-15).
Set the Rectifier turn ON threshold (ON THRESH): This field
allows you to set the rectifiers’ turn-on threshold value. This value is
applied to all the rectifiers in the system. If the voltage is below this
threshold, the rectifiers will be turned ON automatically. Use the <+>,
<-> key to change the value, the step is 0.10 Volt, press <ENTER> to
save the value.