Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Configuration 4 - 43
RMOVE CONV: May be used to remove a converter from the
configuration. The converter number is selected using <+> and <-> keys
and <ENTER> will remove the specified converter from the
configuration. Removing a converter will cause all associated alarms
generated by that converter to be filtered and ignored by the Galaxy SC.
ADJ PL VOLT: This field allows you to calibrate the converter voltage
that monitored on a separate VOM. For example, if the Galaxy SC
shows that the converter voltage is 48.26V, and your meter reads
48.30V, you can use this field to adjust the converter voltage display to
48.30V to match your meter reading. You may change the voltage in
steps of 0.01V. The maximum total change is 0.5V in either direction.
The changed value entered will be used to compute other converter
voltage readings, using a linear equation. Use the <+> or <-> key to
change the field value; press <ENTER> to save it.
RST PL VOLT: The next field, RST PL VOLT, allows you to
neutralize the adjustment made to the converter voltage (using the ADJ
PL VOLT field). With the cursor on this field, pressing <ENTER> key
will zero out the calibration for the converter voltage. The voltage value
displayed now is the true value as recognized by Galaxy SC.
EasyView
Software
Communication
Mode
Note: EasyView screens change with different versions of Galaxy
and different versions of EasyView. The EasyView paths shown
here are based on Version 7.3.0 of both Galaxy and EasyView.
Refer to EasyView Software User Manual, Select Code 193-104-105,
for detailed instructions on setting up EasyView in a personal computer
for access to Galaxy SC via the Local or Modem ports. EasyView is a
Windows-compatible communications package designed specifically
for use with Galaxy SC and is the recommended user interface for
accessing, programming and obtaining data from Galaxy SC. This
software package is provided as part of the J85501F1 L-AB or L-AD
Intelligent controller specification.
Figure 4-1 shows the EasyView Main screen which is accessed once the
user has successfully made a connection with Galaxy SC. It includes a
horizontal status bar at the bottom, which displays information
regarding the present controller connection, including Plant Voltage and
Load, the number of Alarms and Warnings, and the current time. The
main section of the display contains a Site Description ID field, and
fields containing detailed descriptions of active Alarms and Warnings.
EasyView’s main menu is located across the top of this screen.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals