Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Configuration 4 - 47
Alarm Cut-Off
Feature
Configure → Alarm Cut-Off (ACO). Controls which relays are
allowed to be turned off by ACO, providing a time-out feature not
configurable from the front panel. See Chapter 7 for additional
information.
DES: Allows modification of the default designation.
Critical ACO: Enables or Disables the Critical relay ACO.
Critical ACO Time out: User defined time-out of 1 to 4 hours.
Major ACO: Enables or Disables the Major relay ACO.
Major ACO Time out: User defined time-out of 1 to 4 hours.
Minor ACO: Enables or Disables the Minor relay ACO.
Minor ACO Time out: User defined time-out of 1 to 72 hours.
Alarms Overview All alarms in the system whether Standard, Threshold or User Relay
type can be configured to change their default parameters at the users
discretion. Each alarm can be individually configured to utilize the Call
Out on Alarm feature of the controller, which is discussed in detail in
Chapter 7. The following parameters are configurable
DES: Allows modification of the default designation.
Severity: Choice of: Critical, Major, Minor, Record Only or Warning.
Choosing Critical, Major and Minor operate the corresponding alarm
relay.
LED: Choice of: AC, BATT, BD, CTLR,DIST, RECT, or RM LEDs
which illuminate when the alarm is asserted.
RELAY: Choice of ACF, BD, CTLR, HV, MJF, MNF, RFA, UR1,
UR2 and UR3 (VLV) that will operate when the alarm is asserted. UR1,
UR2 and UR3 (VLV) are not available when low voltage contactors are
used in the system unless GPS BIC cards are also used.
Call Out Notify On Occur: Enables or disables call-out upon the alarm
assertion.
Call Out Notify On Retire: Enables or disables call-out upon the alarm
retiring.