Tyco Electronics Galaxy SC Controller J85501F-1
4 - 48 Configuration Issue 13 February 2001
Nag On Occur: Enables or Disables the Nag feature which will
consistently re-call the destination numbers if the alarm persists.
Notify Delay: Provides a delay time of 0 to 540 seconds before calling
out. If the alarm retires prior to the delay period ending, no call is made.
Notify Destinations: User may select as many as four of the configured
phone number destinations to report to.
Connected
Equipment Alarms
Configure → Alarms → Connected Equipment Alarm. Configures
the alarm parameters for up to four controllers or monitoring units that
are optionally connected via an RS-232 link to the controller’s Data
Switch ports. The LED and Relay parameters are not configurable.
Standard Alarms Configure → Alarms → Standard. Allows modification of the default
configuration and call-out assignments for all alarms shown in Tables
4-B and 4-C.
Threshold Alarms Configure → Alarms → Threshold. Allows modification of the
default configuration and call-out assignments for all voltage threshold
alarms shown in Table 4-A. In addition several other alarms having
different types of thresholds are shown below.
Excess Rectifier Drain: Default threshold is set at 1.18 times the
rectifier capacity. The controller monitors each connected rectifier for
this possible alarm.
Engine Transfer Time out: Default threshold is 30 minutes for the ac
transfer equipment to assert the ETR leads, placing the rectifiers in
standby.
Limited Recharge: Default threshold is set at 80% of total rectifier
capacity. Plant load exceeding this value, asserts the alarm.
Multiple Rectifier Fail: Default is set at 2 rectifiers failing
simultaneously.
Rect / Plt Drain Inconsistency: Default is set at 1.05 times the total
rectifier drain. If plant load exceeds this value the alarm is asserted.
Reserve Time Low: Default is set at 2 hours.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals