Tyco Electronics Galaxy SC Controller J85501F-1
4 - 56 Configuration Issue 13 February 2001
Call-Out Periodic
Call Out
Configure → Call-out → Periodic Status Call-Out. Configures the
destination phone number and data parameters, baud rate etc., for having
the controller call out to deliver the system status, histories and statistics.
Intervals can be set as a specific day of the week, daily, weekly, monthly
or quarterly. Up to 10 T1.317 commands can be configured to report any
of the available system data.
Passwords Configure → Change Passwords. Allows changing of system
passwords. The user must be logged in at the administrator level to
change passwords.
Data Switch Configure → Data Switch Port 1 / 2/ 3 /4. Sets the parameters
necessary to connect a remote RS-232 device to the optional Data
Switch ports. See the Data Switch feature in Chapter 7 for additional
information.
DC Plant
Hardware and
Software
Configure → DC Plt → Hardware and Software. Several controller
features must be enabled both by Hardware switches located on circuit
packs as well as in software. Both must be enabled for the feature to
operate.
Restart: Enables or disables the software switch for the auto rectifier
restart feature (after an HV shutdown). The associated hardware switch
is SW202-7 on the BJB pack.
Boost: Enables or disables the software switch for the Boost / BTP
feature. The associated hardware switch is SW202-3 on the BJB pack.
Energy Mgmt: Enables or disables the software switch for the Rectifier
efficiency algorithm feature. The associated hardware switch is
SW204-1 on the BJH pack.
Ext Timer Boost: Enables or disables the External Timer Boost feature.
The associated hardware switch is SW202-2 on the BJB pack.
Alarm Test: Enables or disables the software switch for the Alarm Test
feature. The associated hardware switch is SW202-5 on the BJB pack.
Remote Alarm Test: Enables or disables the software switch for the
Remote Alarm Test feature. The associated hardware switch is
SW204-2 on the BJH pack.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals