Issue 13 February 2001 Configuration 4 - 55
Current Term Vltg Thrhld: Sets the voltage trigger/switch used as a
qualifier for QRCT Boost entrance.
Current Term Current Thrld: Sets the total current value flowing into
or out of the battery as a qualifier for the controller to activate QRCT
Boost.
Current/Time Ratio: Sets the absolute value of the gradient
calculation, (change in charge current/change in time). Suggested value
setting is 0.5.
Boost State Alarm: A UDE may optionally be linked indicating boost
is active.
Call Back Security Configure Call Back Security In this feature after the initial modem
connection is made, the remote user designates which of the five
possible configured numbers is to be called back. The controller
disconnects, then calls back the requested number. The five numbers are
configured here, the feature is enabled or disabled and the applicable
baud rate is set.
Call-Out Phone
Numbers
Configure Call-out Call-Out Phone No. Four possible phone
numbers for the call out feature which will report on all designated
alarms or periodically, are configured along with an alternate number
that is called only when the others cannot be reached. The type can be
set as either Data or Pager and a pager ID and delay are defined. Other
fields set Parity, Baud Rate, Data Bits and Stop Bits for each number.
Additional information regarding all Call-Out features, and a pager
example, can be found in Chapter 7.
Call-out to pagers with pin numbers require that the pager companys
TAP or self-dispatch server phone number be used instead of the
normal manual number. The pager's pin number must be entered into the
"Send Message" field, while the number to be displayed is placed into
the "Message" field.
Call-Out Nag
Interval
Configure Call-out Nag Interval. Each system and user defined
alarm can be individually configured to have a NAG interval. The
controller will continuously call out at the interval set here while the
alarm remains active.