Tyco Electronics Galaxy SC Controller J85501F-1
4 - 58 Configuration Issue 13 February 2001
Battery Type: Select from a list of Tyco or Exide battery types. Type
selected is used in the Battery Reserve Time Prediction feature.
Inst Cells per String: Number of cells in the battery string is used in the
Slope Thermal Compensation feature.
Inst Strings per Plt: Number of battery strings is used in the Slope
Thermal Compensation feature.
Rect On Thld: Sets the battery voltage at which all rectifiers that are
being held off by the controller are released to operate. (After the
Rectifier On Delay, below.)
Rect On Delay: Sets the time delay after the Rect On Thld above, is
reached that all rectifiers that are being held off by the controller are
released to operate.
Rect Sequencing: Enables or Disables the internal rectifier sequencing
feature during ac transfer from commercial to emergency bus. This
feature also requires connection to a contact closure transition (open,
close, open) during the transfer at TB3 12/13 (ETR and ETRR).
Initial Trsfr Delay: Delay time (1 to 600 seconds), after the contact
closure transition above, after which the rectifiers will begin to be
released. The interval will default to 1 second regardless of the setting
of this field unless a closure is recognized across the RO/ROR pair
(TB3-14/15), indicating that a gen-set is supporting the ac load.
Trsfr Seq Interval: Delay time (.1 to 600 seconds) between the releases
of each succeeding rectifier. The interval will default to 1 second
regardless of the setting of this field unless a closure is recognized
across the RO/ROR pair (TB3-14/15), indicating that a gen-set is
supporting the ac load.
AC Distribution
Links
Configure → Distribution → AC. This configuration allows the
linking of RPM channels to pre-defined objects associated with the ac
service.
PH1, PH2, PH3 Voltage: Voltage RPM channels, (transducers
required) can be linked to monitor the phase to neutral ac voltages.
PH1, PH2, PH3 Current: Voltage RPM channels, (transducers
required) can be linked to monitor the phase currents.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals