Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Operation 6 - 17
Viewing Active
Alarms
The T1.317 interface allows 3 commands that allow viewing of active
alarms. Which command is used depends on the programmed severity
of the alarm. If the severity is record-only the REC command is used to
retrieve the active alarms referred to as record-only events. If the
severity is warning then the WAR command is used to retrieve the
active alarms referred to as warnings. If the severity is critical, major, or
minor then the ALA command is used to retrieve the active alarms. See
the T1.317 command language description for details regarding the
syntax of these commands. The examples below illustrate how these
commands may be used to retrieve active alarm information:
Battery
Management
The T1.317 interface allows full configuration and management of
batteries as supported by the Galaxy SC. Battery configuration is done
in three steps:
Build the battery configuration.
Link remote monitoring channels to battery attributes.
Parameter configuration.
Some configuration steps may be omitted depending on the needs of the
system. For example, the first step, building battery configurations,
serves as an organizational tool and is not necessary in most cases. If the
SAPO interface is being used, however, this first step is essential.
Building Battery
Configurations
The T1.317 interface supports building battery configurations in bays
and sections. The commands below show how to build a battery
configuration made up of a single battery bay with two battery sections:
ADD BBY,BB01 add battery bay BB01
ADD BAT,B01 add battery section B01
ADD BAT,B02 add battery section B02
LIN BB01 BAT, B01, B02 link battery sections B01 and B02 to
battery bay BB01
Linking Remote
Monitoring
Channels
The following command will cause the temperature measured by remote
peripheral monitor channel C107 to be reported as the temperature for
battery bay BB01.
LIN BB01 TMP,C701 link temperature monitor C701 to the
battery bay temperature attribute
The following commands will create the links needed for full battery
management. The examples below are for reference only. Actual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals