6 - 20 Operation Issue 13 February 2001
contactor 1 or contactor 2 and to set the battery high temperature
disconnect threshold.
Clearing Active
Alarms
Some alarms are latched, meaning that once they occur they must be
cleared manually. These alarms can be cleared individually using the
CLE command. Below is a list of these alarms:
Standard alarms: EPR1, EXL1, CLC1, STF1, CCH1, HCL1,
EPD1, COF1, COR1, POR1, ATF1, ATB1
Threshold alarms: LMR1, ERD1, RPI1
All maintenance reminders
All user defined events with the latched attribute (LAT) equal to 1
Configuration
Backup
To backup the system configuration from a T1.317 interface follow the
procedure below:
1. Login as a super-user.
2. Enter the BACKUP command.
3. Select either Xmodem or ASCII transfer.
4. Start your terminal Xmodem or ASCII download program.
5. during an ASCII transfer, hit any key to indicate that you are ready
for the data.
The backup session will terminate automatically with a message
indicating that the backup was completed or not. Reference the T1.317
object tables in the appendix for details regarding which attributes are
included in the backup and which are not. As a rule of thumb attributes
that can be configured using the CHA command are included in the
backup. Exceptions to this rule are the system date and time. All objects
and linkable attributes added by the user are backed up. Any links
created by the user are also backed up. Aliases defined by the user are
also backed up. All configuration data is also permanently stored in the
controller. This configuration will be used as the new default on
subsequent power-on sequences if the backup battery power is lost.
Configuration
Restore
To restore a system configuration from a T1.317 interface follow the
procedure below: