Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Operation 6 - 19
The T1.317 interface also allows the user to configure the battery slope
thermal compensation feature. The follow commands demonstrate how
to do this:
CHA SC1,STT=1 Change the slope thermal compensation
state to enabled
CHA SC1,RVE=0 Change the reduce voltage enable state to
enabled
CHA SC1,UTT=45 Change the upper temperature threshold
to 45 degrees
ALA Retrieve all active alarms in the system
WAR DC1 Retrieve all active warnings linked
to the DC plant
REC PS1 Retrieve all active record-only events
linked to the power system object
Contactor
Management
The T1.317 interface allows configuration and management of the low
voltage disconnect contactors. The following commands show how to
configure contactor 1 as a battery low voltage contactor:
CHA CN1,TYP=“BATTERY”
change contactor typebattery contactor
CHA CN1,DTH=44 change the disconnect threshold to 44 V
CHA CN1,RTH=48 change the reconnect threshold to 68 V
To operate a battery contactor use the following commands. Note that
these commands will only work if both contactors are configured as
battery contactors.
OPE CN1,STT=“DISCONNECT”
operate the contactor to the disconnected
state
OPE CN1,STT=“CONNECT”
operate the contactor to the connected
state
The following commands are useful for querying the state of the
contactors:
ALA CNT report all contactor active alarms
STA CN1,STT report state of contactor 1
STA CN2,STT report state of contactor 2
See the manual section entitled “T1.317 Battery Management” for
details on configuring a battery section to be associated with either