ADD DBI,DI1 add distribution bay inventory 1
to the system
ADD DI1,PIN add a linkable attribute called PIN
to the bay inventory
ADD PIN,PI01 add panel inventory called PI01
LIN DI1 PIN,PI01 link the panel inventory to the bay
inventory at PIN
ADD PI01,SLI add a linkable attribute called SLI
to the panel inventory
ADD SLI,SLI001 add a slot inventory called SLI001
LIN PI01 SLI,SLI001 link the slot inventory to the panel
inventory at SLI
A similar set of commands would be needed to build the reserve battery
inventory with battery strings. Use the following command to add a
controller option inventory object to the system:
ADD COI
Because this command does not specify a specific controller option
inventory object identifier, the command will respond with the identifier
of the object added to the system. If this was the first controller option
inventory to be added the identifier would be CI01. The following
command sets the install date of the controller option to 05/20/95:
CHA CI01,IDT=“05/20/95”
Other attributes in the inventory can be changed by substituting CI01
with the inventory object’s identifier, IDT with the attribute mnemonic,
and “05/20/95” with the desired text. Remember that all inventory
attributes are text and should be enclosed in double quotes.
Maintenance
Reminder
Management
From the T1.317 interface the maintenance reminders can be viewed
and configured. Maintenance reminders are identified by the
mnemonics MR01 through MR12. The following examples illustrate
how to program a maintenance reminder:
CHA MR01,DAT=5/20/95 change notification date to 5/20/95
CHA MR01,TIM=1:30am change notification time to 1:30am
CHA MR01,TXT=“Service the batteries”
change the notification text
These commands will cause a maintenance reminder warning to occur
at 1:30am on May 20, 1995. When the warning is reported by the WAR
command, the text “Service the batteries” will be displayed in place of