Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Operation 6 - 29
the warning description. To configure other maintenance reminders,
replace MR01 with the proper identifier and change the date, time, and
text accordingly. Warnings can also be configured to call out. See the
object tables in Appendix B for a complete list of maintenance reminder
mnemonics including those programmed for call out.
To clear a maintenance reminder once it has occurred use the following
command:
CLE MR01
Notepad
Management
From the T1.317 interface both the user and super-user notepads can be
viewed and configured. The mnemonic UNP is used to reference the
user notepad and SNP is used to reference the super-user notepad. The
notepad comment lines are configured a line at a time. The following
examples illustrate how this can be done:
CHA UNP,CL01=“*** NOTIFICATION ****”
CHA UNP,CL02=“On Thursday the plant will be undergoing
maintenance.”
These commands configure line 1 and 2 of the user notepad. To
configure the super-user notepad, login as super-user and substitute
UNP with SNP. The login header indicates whether there is a user or
super-user notepad message that should be read. The header contains the
lines:
:UNP
STT=0
:SNP
STT=0
These lines indicate the state of the user and super-user notepad state
attribute identified as STT. To set the state to 1 use the following
command:
CHA UNP,STT=1
The following command will display all the notepad attribute values
including the comment lines:
STA UNP