Periodic Status
Call-Out
Configuration
From the T1.317 interface the periodic status object, identified as PO1,
can be viewed and configured. See the T1.317 object tables in Appendix
B for attribute mnemonics and other details. The following example
illustrates how to configure periodic status call out:
CHA PO1,PHN=“222-3333” change phone number to 222-3333
CHA PO1,BDR=9600 change baudrate to 9600
CHA PO1,DBT=8 change data bits to 8
CHA PO1,PRY=N change parity to none
CHA PO1,SBT=1 change stopbits to 1
CHA PO1,INT=“MONTHLY” change the interval to monthly
CHA PO1,TIM=“5:30am” change the time to 5:30am
CHA PO1,CL01=“HEADER” set the first command line to
report the HEADER
CHA PO1,CL02=“ALA;WAR” set the second command line to
report active alarms and warnings
Rectifier Control
Usage
To restart all rectifiers, issue the following command:
OPE DC1,RSS=1
To place a rectifier in the standby mode from the on mode, issue the
following command:
OPE Gnn,STT=STANDBY
where nn = 01 to 64, identifying the particular rectifier to put in the
standby mode
To place a rectifier in the on mode from the standby mode, issue the
following command:
OPE Gnn,STT=ON
where nn=01 to 64, identifying the particular rectifier to put in the on
mode
To view the rectifier diagnostics, issue the following command:
DIA REC
To view the history of rectifier state changes, issue the following
command:
HIS REC,STT