6 - 32 Operation Issue 13 February 2001
The following commands are examples that illustrate how to configure
the float mode thresholds for serial interface rectifiers and enables load
sharing:
CHA GM1,LSE=1 enable digital sharing state to enable
CHA GM1,FSD=60 change the high voltage shutdown
threshold to 60 V
CHA GM1,FSP=52.08 change the float set-point to 52.08 V
CHA GM1,FCL=105 change the float current limit threshold
to 105%
In addition to configuring rectifier parameters, the T1.317 interface
allows the user to organize rectifiers into bays. This is not necessary for
normal rectifier operation except when using the SAPO interface.
The following commands show how to build a rectifier bay with 2
rectifiers. For help creating user defined events please see the section
entitled T1.317 User-Defined event Management in this manual.
ADD RBY,RB1 create a rectifier bay
LIN RB1 REC,G01,G02 link rectifier 1 and 2 to the rectifier bay
LIN RB1 ICB,U0001 link user-defined event 1 as the
rectifier bay input circuit breaker state
LIN RB1 TMP,C701 link a remote peripheral monitor as
the bay temperature source
Remote Peripheral
Monitor
Management
To support remote peripheral monitoring, the T1.317 interface provides
module objects and channel objects. This section describes how to view
and set some of the module and channel attributes. For a complete list of
attributes see the object tables in Appendix B of this manual. Listed
below are identifiers of the remote peripheral module and channel object
types:
RPM Remote Peripheral Monitor Module Types
VTM Voltage Monitor Channels Types
SHM Shunt Monitor Channels Types
TPM Temperature Monitor Channels Types
The module object identifiers start with an M followed by two
characters that indicate the modules address. For example, the identifier
for the module at address 24 is be M24. The channel identifiers start
with a C followed by a channel specifier and module address. For
example, the identifier for channel 4 on the module at address 24 is
C424. To view a list of the channels that exist in the system, it is useful

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals