EasyManuals Logo

Tyco Galaxy SC Controller User Manual

Tyco Galaxy SC Controller
413 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #208 background imageLoading...
Page #208 background image
Tyco Electronics Galaxy SC Controller J85501F-1
6 - 34 Operation Issue 13 February 2001
MET G01
MET G01,LOAD
Reserve Time
Prediction
This section describes how to configure and view the parameters that are
related to the reserve time prediction algorithm. The reserve time
parameters are all attributes of the DC Plant object identified as DC1.
The examples below illustrate how to change and view these
parameters:
STA DC1, RTM report the reserve time
CHA DC1,NST=4 change the number of battery strings to 4
CHA DC1,CPS=24 change the number battery cells
per string to 24
CHA DC1,BTY=IR-125change the battery type to IR-125
STA DC1,TPP report if temperature probe is present
(0:no 1:yes)
STA DC1,UBT report the universal battery temperature, if
present
STA DC1,TRD report the total rectifier drain
STA DC1,VDC report the plant DC voltage
STA DC1,ADC report the plant DC current
The Reserve Time Too Low alarm is identified as RTL1 and is linked to
the DC plant object. The example below illustrates how the alarms
threshold can be set and how to check if the alarm is active:
CHA RTL1,THR=3 change the reserve time too low
threshold to 3 hours
ALA DC1 report active DC plant alarms
To view the battery on discharge history, which includes the reserve
time at the beginning of discharge, use the following command:
HIS DC1,BOD report the battery on discharge history
Security Level and
Password
Management
To change security levels from the T1.317 interface use the LOGIN
command with either the user, super-user, or administrator passwords.
Normally, only one login as the super-user or administrator level is
allowed at a time. If an attempt is made to login as a super-user while
someone else is logged in as a super-user or administrator this error
message will be reported:
-226, ONE SUPER-USER/ADMINISTRATOR ALLOWED

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals