Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Feature Descriptions 7 - 58
• Binary mathematical operators accepted: (+, -, *, /).
• Unitary mathematical operators accepted: (+, -).
• Comparator operators accepted (= EQ, < LT, > GT).
• Parentheses accepted.
• The expression has the following precedence (highest first):(),
NOT, unary +, negation -, *, /, +,-,, <, >, EQ, AND, XOR, OR.
The follows are acceptable operands:
• Numbers are accepted.
• Plant analog attributes: dc1 vdc (plant voltage), dc1 adc (plant
current), dc1 trd (total rectifier drain, dc1 ubt (plant universal
battery temperature).
• Rectifier current attribute: gxx adc, where xx is from 01 to 24 (for
24 rectifiers).
• Remote monitor value attribute: cxyy val, where x is from 1 to 7, yy
is from 01 to FF.
• Remote monitor state and alarm attributes: Cxyy ATR, where x is
from 1 to 7, yy is from 01 to FF (Hexadecimal number); ATR is
MOR (for Measure Out of Range alarm), MDF (Module Fail
alarm), MTC (for Module Type Conflict alarm), or STT (for
module state, which has a value of 0 if module is connected and
good, 1 otherwise).
• Derived channels value attribute: dxx val, where xx is from 01 to
32.
• Timer Events state as binary value: Txx stt, where xx is 01-32.
• User defined event alarm state: Uxxxx ast, where xxxx is
0001-1500.
• All system alarm state: alarm ast, where alarm is:
A1: Controller Fail LVD1: Low Voltage
Disconnect
RF1: Controller Fuse OSA1: Open String
CPA1: Circuit Pack Fail EMD1: Energy
Management
Disabled
RPF1: Remote Peripheral Fuse EPD1: Excess Plant Drain
PCF1: PC Power Fuse SNC1: Shunt Not
Configured
EPR1: External Password Reset RFA1: Rectifier Fail
PFD1: Password At Default ACF1: AC Fail
EXL1: Excessive Login Attempt PHA1: Phase Or Low
Output
BBL1: Memory Backup Battery LCA1: Low Current