EasyManuals Logo
Home>Tyco>Controller>Galaxy SC Controller

Tyco Galaxy SC Controller User Manual

Tyco Galaxy SC Controller
413 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #335 background imageLoading...
Page #335 background image
Tyco Electronics Galaxy SC Controller J85501F-1
Appendix A - 8 T1.317 Interface Issue 13 February 2001
from the list of objects being linked to it. The following example adds a user de-
fined event to the power system manager object, PS1, and sets its severity to
minor:
ADD UDE,U0001 Add a user defined event identified as U0001
ADD PS1,RMHOT Add a linkable attribute called RMHOT to PS1
LIN PS1 RMHOT,U0001
Link U0001 to PS1 at the RMHOT linkable
attribute
CHA PS1 RMHOT,SEV=MIN
Set the RMHOT event severity to minor
This example results in the user-defined event called U0001 being reported as
the power system manager alarm RMHOT.
LOGIN Login at a security level
Syntax:LOGIN [password]
This command allows the user to change security levels. If the password is not
include in the command line, this command responds with an ENTER PASS-
WORD: prompt. The user is then given 3 tries to enter the password of the us-
er, super-user, or administrator security level. If the wrong password is entered
the controller will respond with INVALID PASSWORD followed by the pass-
word prompt. After three unsuccessful password attempts the Galaxy will log
off and report excess login attempts condition.
OPE Change the state of special operational attributes
Syntax:OPE objpath,attrid=value
The state of certain attributes are changed using this command instead of the
CHA command. These attributes will initiate some special function or operating
mode. The command may or may not require the super-user security level.
The examples below illustrate how to change the operational attributes in the
system:
OPE DC1,STT=FLOATSet DC plant 1 state to float
(super-user security)
OPE DC1,RSS=1 Initiate a DC plant 1 rectifiers restart
(user security)
OPE REC,STT=ON Turn all rectifiers on (user security for on,
super-user security for standby)
OPE ACO,STT=1 Alarm cut-off (user security)
OPE ATS,STT=1 Initiate an alarm test (user security)
OPE DS1,STT=pass-thru
Pass-thru to data switch 1 (user security
for PASS-THRU)
Note the following command is not allowed in the Galaxy controller:
OPE REC,STT=STANDBY
PAGE Set the command response page length in lines for current
session
Syntax:PAGE number
For this command, if number is between 1 and 99, paging is enabled and com-
mands will respond with no more than number lines of data at a time. After re-
sponding with a page of data the controller will respond with:
<SPACE> to continue, other to cancel...
If the user presses the space bar the controller will respond with the next page
of data. If the user presses any other key, the rest of the command output will
not be sent to the terminal. If number is set to 0, paging is cancelled. The page
setting is set back to 0 when a user logs off.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals