Tyco Electronics Galaxy SC Controller J85501F-1
Appendix A - 14 T1.317 Interface Issue 13 February 2001
active record-only events are reported. Each line in the report has the following
format:
event_path,date,time,severity,description
The following examples will report all the active record-only events in the sys-
tem and just the DC plant active record-only events:
REC
REC DC1
STA Reports the value of an attribute
Syntax:STA objpath<,<attrid | attrl>>*
This command is useful for reporting the values of attributes of objects that ob-
jpath leads to. For linkable attributes this command will report the objects
linked to the attribute. If attributes are included in the command line, the report
is limited to those attributes. The report will include the object identifier preced-
ed by a colon followed by a line for each attribute in the following format: at-
trid=value. The following examples reports the status of all rectifier G01
attributes and then just the status of the type attribute for all rectifiers:
STA G01(alternate syntax: STA DC1 REC G01,STT)
STA REC,STT(alternate syntax: STA DC1 REC,STT)
The alternate syntax illustrates that the full path object may be used in the com-
mand line. The alternate syntax illustrates that rectifiers are linked to DC1 at
the REC limitable attribute.
SUM Report statistical data
Syntax:SUM objpath<,<attrid | attrl>>*
This command is useful for reporting the statistics data for measurement at-
tributes of objects that objpath leads to. Examples of measurement attributes
are plant voltage and plant current. The object tables in the appendix indicate
which attribute are measurements. In addition, linkable attributes linked to re-
mote peripheral monitor channels are considered measurement attributes. If
attributes are specified in the command line, those attributes must be mea-
surement attributes. If linkable attributes are specified on the command line,
those attributes must be linked to a remote peripheral monitor channel.
This command is also used for reporting battery on discharge, trend, and busy
hour statistics. Examples of these commands are listed below:
SUM DC1,BOD-report battery on discharge statistics
SUM TR1-report trend 1 statistics
SUM BH1-report busy hour 1 statistics
WAR Report active warnings
Syntax:WAR [objpath]
This command searches the objects that objpath leads to, and all objects
linked to these objects, for active warnings. If objpath is omitted, all active
warnings are reported. Each line in the report has the following format:
event_path,date,time,severity,description
The following examples will report all the active warnings in the system and just
the DC plant active warnings:
WAR
WAR DC1
System Defined
Aliases
The following are aliases defined by the system. They provide a
measure of compatibility with the MCS and PEERS commands. Users
may create their own aliases by using the ALI command. Included in
parenthesis is the T1.317 command line that these commands alias.
ALMS Report all active alarms. (ALA)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals