Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 T1.317 Objects and Attributes Appendix B - 5
Table B-4: Alarm Test Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Alarm Test ATS
Identifier IDE TEXT AT1
Description DES TEXT X X X Alarm Test 1
Alarm Test State STT NUMBER X X 0:inactive 1:active
Rectifier Test Failure RTF TEXT list of rectifiers not passing alarm
test
Alarm Test Enable LTE NUMBER X X X 0:disable 1:enable (HW,SW)
Remote Alarm Test Enable RTE NUMBER X X X 0:disable 1:enable (HW,SW)
HV Shutdown HVS NUMBER X X X 0:disable 1:enable (HW,SW)
Duration DUR NUMBER X X X 5-300:60 seconds
Test Power Critical PCR NUMBER X X X 0:no 1:yes
Test Power Major PMJ NUMBER X X X 0:no 1:yes
Test Power Minor PMN NUMBER X X X 0:no 1:yes
Test Major Fuse MJF NUMBER X X X 0:no 1:yes
Test Minor Fuse MNF NUMBER X X X 0:no 1:yes
Test Battery on Discharge BD NUMBER X X X 0:no 1:yes
Test AC Fail ACF NUMBER X X X 0:no 1:yes
Test Rectifier Fail Alarm RFA NUMBER X X X 0:no 1:yes
Test Very Low Voltage VLV NUMBER X X X 0:no 1:yes
Test High Voltage HV NUMBER X X X 0:no 1:yes
Test Controller CTLR NUMBER X X X 0:no 1:yes
Test User Relay 1 UR1 NUMBER X X X 0:no 1:yes
Test User Relay 2 UR2 NUMBER X X X 0:no 1:yes
Alarm Test Active ATA ATTRL ATA1
Alarm Test Failed ATF ATTRL ATF1
Alarm Test Aborted ATB ATTRL ATB1