Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 6 T1.317 Objects and Attributes Issue 13 February 2001
Table B-5: DC Plant Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
DC Plant DCP
Identifier IDE TEXT DC1
Description DES TEXT X X X DC Plant 1
Plant Type TYP NUMBER +48V/ +24V/ -48V/ -24V DC
Voltage VDC NUMBER X X number V
Current ADC NUMBER X X number A
Capacity CAP NUMBER number A
Total Rectifier Drain TRD NUMBER X number A
Shunt Type SHT TEXT X X X LOAD, BATTERY, NONE
Shunt Current SHA NUMBER X X X 0-4,294,967,295 A
Shunt Voltage SHV NUMBER X X X 1-150 mV
State STT TEXT X X FLOAT, BOOST (if BTP=0), BTP
(if BTP=1)
Backup HV Threshold BHV NUMBER number V
Battery On Discharge BOD NUMBER 0:no BD 1:BD active
Energy Management State EMS NUMBER 0:off 1:on
Energy Management Enable EME NUMBER X X X 0:disable 1:enable (HW,SW)
Restart State RSS NUMBER X X 0:off 1:on
Restart Enable RSE NUMBER X X X 0:disable 1:enable (HW, SW)
Rectifier Sequencing RSQ NUMBER X X X 0:disable 1:enable
All Rectifier On Threshold ROT NUMBER X X X 20-25:22 or 40-50:44 volts
Rectifier On Delay ROD NUMBER X X X 0-60:10 minutes
Transfer TRF NUMBER 0:inactive 1:active,...,0:inactive
1:active
Initial Engine Transfer Delay ITD NUMBER X X X 1-600:1 seconds
Transfer Sequence Interval TSI NUMBER X X X 0.1-600:1.0 seconds
Battery Therm. Integrity BTI NUMBER 0:detached 1:attached
Universal Battery Temperature UBT NUMBER X number C
Universal Temp Probe Present TPP NUMBER 0:no 1:yes
Number of Strings NST NUMBER X X X 1-70:2
Number of Cells per String CPS NUMBER X X X 1-75:12 (24V plant) or 24 (48V
plant)
Plant Battery Type BTY TEXT X X X
L-1S,IR-30,IR-40,12IR-125,4VR-
125,2VR-375,L-508,GU-41,GU-45
default: “”
Reserve Time RTM TIME hh:mm
Alarm Sub-Objects
Battery Thermal Major BTJ ATTRL BTJ1
Battery Thermal Minor BTN ATTRL BTN1
Auxiliary Fuse Major AMJ ATTRL AMJ1
Auxiliary Fuse Minor AMN ATTRL AMN1
External Fuse Major FAJ ATTRL FAJ1
External Fuse Minor FAN ATTRL FAN1
Regulation Battery Fuse RBF ATTRL RBF1
Batt Thermal Fuse BTF ATTRL BTF1
Battery Power Fuse BPF ATTRL BPF1
Alarm Battery Supply ABS ATTRL ABS1
Sense/control Fuse VSF ATTRL VSF1
Low Voltage Disconnect Fail LVDA ATTRL LVDA1
Low Voltage Disconnect LVD ATTRL LVD1
Open String OSA ATTRL OSA1
Energy Management Disabled EMD ATTRL EMD1
Excess Plant Drain EPD ATTRL EPD1
Shunt Not Configured SNC ATTRL SNC1
User Relay Conflict URC ATTRL URC1
ID Not Configured ZID ATTRL ZID1
Thermal Probe Failure TPA ATTRL TPA1
Minor Comm Fail Alarm CMA ATTRL CMA1
Major Comm Fail Alarm MCM ATTRL MCM1
Bay Interface ID Conflict BID ATTRL BID1
Rectifier Fail RFA ATTRL RFA1
AC Fail ACF ATTRL ACF1
Phase or Low Output PHA ATTRL PHA1
Low Current LCA ATTRL LCA1
Load Share Fuse LSF ATTRL LSF1
Manual Off MAN ATTRL MAN1
External Transfer Shutdown ETS ATTRL ETS1