UniPOS IFS7002 two signal loops
Instruction Manual Page 10
Revision 11/01.17 Of 145
nominal voltage of the back up battery - 24V
nominal capacity C
20
- 18Ah
extreme discharge voltage - 21V
charge voltage - 28,2V
4.10.3. Consumption on back up batteries supply
at 24V - < 250mA
at 26V - < 240mA
4.10.4. Power supply to external devices
Voltage - (24±5)V
Maximum current value (including current
of monitored outputs and power loop) - 5А
4.11. Dimensions
Overall dimensions - 480x445x100mm
4.12. Weight
Weight (batteries not included) - 7,1kg
5. Contents of delivery
Fire control panel IFS7002 - 1 pc
Resistors 5,6k/ 0,25W - 2 pcs
Jumper for the backup batteries - 1 pc
Fuse 4A - 1 pc
Fuse 6,3A - 1 pc
Instruction manual - 1 pc
Instructions for authorized staff - 1 pc
Packing - 1 pc
6. General information
The stylus (pos.1, fig.1) is provided for
comfortable and safe operation of the touch-
screen of the IFS7002 fire control panel and
IFS7002R.
Use the stylus by slightly pressing its tip onto
the area of the designated button.
The self-adhesive pad of the carrier ( pos.2,
fig.1) allows for easy fixation at the proper place.
The recommended place on the fire control
panel IFS7002 is displayed on Fig. 2.
Usage of other objects for touch-screen
operation is not recommended due to possible
damage
6.1. Access levels
4 levels of access to the variable indications and control functions of IFS7002 are available.
6.1.1. Access Level 1
All persons who would presumably find out and react to alarm upon fault condition or fire
condition have access to level 1.
The following actions are accessible:
Displaying suppressed messages for Fire condition, Fault condition, Disabled
components and Zone in test (see sections 8.3.6, 12.2.1, 12.2.2 and 12.2.3);