UniPOS IFS7002 two signal loops
Instruction Manual Page 25
Revision 11/01.17 Of 145
Upon Battery Low condition - full
discharge of the backup batteries
due to interrupted power supply – the
following information screen appears:
The screen suppresses all other
text indications, with the exception of
System error message, and can not
be suppressed.
For all other fault conditions a
table, containing information on the
number of fault events and the
number of disabled devices is
displayed. The first line of the tables’
left column displays the total number
of fault conditions; the first line of the
table’s right column displays only the
number of faults in outputs
(monitored outputs and addressable
output devices):
To display the text message for
each fault condition, enter
Information and Control Mode (see
section 12.2.1).
9.3. Using the keypad
None of the buttons is active upon fatal fault condition. For all other fault condition 2 buttons are
being supported. Where the fire control panel operates in combination of other conditions, their
buttons are active too.
9.3.1. Button (Stop Alarm)
The button appears on the LCD display where the fire control panel enters fire condition in a new
zone or a new fault condition occurs; it disappears if pressed or if the sound signaling is suspended
(fault conditions suspended and/or fire control panel exited fire condition)
Press the button to switch the local sounder off.
The button does not affect and is not influenced by the following events:
Fire condition in new zone or transition from phase Fire condition stage I to Fire condition
stage II will trigger the local sounder and a signal for fire condition only will be produced;
New fault condition will trigger the local sounder and a signal for fault condition only will be
produced.
9.3.2. Button (Menu)
Press the button to enter Information and Control Mode.
FIRE CONTROL PANEL IFS7002
UniPOS
Thu 11 Feb 2010
11:43:13
Faults Total: 00001/00000*
Disables Total: 000
Failed Outputs: 0000
Disabled Outputs: 000