The unit shall be excluded from the Service zone, via Menu “Re-addressation” (see section
13.9.3) and the suitable address shall be assigned;
The new loop configuration shall be saved through Function “Clear Initialization” (see section
13.9.2).
When new addressable unit is included in a loop set to automate addressing, (exceeding the total
number of addressable units in the loop), the fire control panel assigns a temporary address
(message seen in the bottom part of the display - Re-initialization), but ignores it in its operation. To
add the unit to the loop configuration the function Clear Initialization shall be activated (see
section 13.9.2).
When new addressable unit is added to a loop set to manual addressing, the fire control panel
ignores it in its operation. To add the unit to the loop configuration the Function Manual Addressation
shall be activated (see section 13.4.5).
When the fire control panel is in Fire condition or in Fault condition or in a combination of one of
these, the lighting of the display is constantly on, until you press button Stop alarm (with the
exception of these fault conditions – Battery low, discharged batteries due to interruption of mains
supply, and Fault in mains supply). Upon Battery low the lighting of the display is constantly off. In all
other cases the lighting is extinguished 3 min after the last pressing of any button on the display.
7. Duty Mode
7.1. Description
The fire control panel is in Duty Mode, when it is not in any other of the rest 6 possible conditions.
7.2. Indication
7.2.1. LED and sound indication
In Duty Mode the green LED indicator is activated (Power supply). The local sounder is off.
7.2.2. Text message
The display shows the logo of
the company-producer, information
on the current local time and the
mode of operation of the fire control
panel (DAY or NIGHT), the mode of
control (Loc – control of local panel,
or RemX – control of a remote panel,
where X is the panel’s address:
7.3. Using the keypad
The only accessible button in Duty Mode is (Menu). Press it and the fire control panel
enters Information and Control Mode.
8. Fire condition
8.1. Description
The fire control panel enters Fire Condition after a fire detector has been activated in one of the
fire alarm zones. In Mode:DAY the condition has two phases – Fire condition stage I and Fire
condition stage II. The time period for Fire condition stage I is limited and is user programmable,
separately for each zone (up to 255 seconds). The period can be prolonged with the Inspection time
FIRE CONTROL PANEL IFS7002