CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL
21
7.3.10 Dew point margin
The Dew point margin can be set if the Climate Controller C-46
is set up in any Cooling mode.
Parameter values:
Default setting: 4
Parameter range: 1–10
7.3.11 Dew point offset
The Dew point offset can be set if the Climate Controller C-46
is set up in any Cooling mode.
Parameter values:
Default setting: 0
Parameter range: -5 to +5
7.3.12 Calculated dew point
The dew point is the
temperature when water
vapour in the air condenses
into water. The dew point is
calculated by the Climate
Controller C-46.
This screen is displayed if the Climate Controller C-46 is set up in
Cooling – fixed supply with dew point control mode.
7.3.13 Idle setpoint
The Idle setpoint can be set if the Climate Controller C-46 is set
up in Meltaway mode.
Setpoint values:
Default setting: 8 °C
Setpoint range: 3–30 °C
7.3.14 Melting supply
setpoint
The Melting supply setpoint can be set if the Climate
Controller C-46 is set up in Meltaway mode.
Setpoint values:
Default setting: 30 °C
Setpoint range: 3–45 °C