CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL
29
8.6.6 Cooling activation
When the Climate Controller C-46 is working in Cooling or
Heating and cooling mode it is possible to set the Climate
Controller C-46 to be either always active or to utilize a winter
shut-off mode.
To set the cooling activation mode:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > Control settings > Cooling >
Cooling activation
2. Select Winter shut-off
or Always active and
press OK to confirm the
selection.
• If the mode Winter
shut-off is selected,
then the menu Winter shut-off is displayed. See
section below.
• If the mode Always active is selected, then the screen
returns to the Cooling menu.
Winter shut-off
The winter shut-off function is used to save energy during the
period of the year when cooling is not necessary. This will save
energy as the circulation pump will not be running.
Some use cases are given in section 10.3
Heating summer shut-
off and cooling winter shut-off, page 47.
To set the winter shut-off parameters:
1. Navigate through the screens:
Uponor > Main menu > Control settings > Cooling >
Cooling activation > Winter shut-off
Example screen:
2. Select
Act./deact. temp.
3. Set the parameter to the
required value and press
OK.
4. Select Delay.
5. Set the parameter to the
required value and press
OK.
6. Select Shut-off enable
period.
7. Set the Start and End
parameter to the required
values and press OK.
Note: Setting the start and end dates to be the same means
that the shut-off function is disabled.
• Default dates: Start = 01 Mar, End = 01 Mar
• Date ranges: Start = any date, End = any date
8.6.7 Dehumidifier control
When the Climate Controller C-46 is working in Cooling or
Heating and cooling mode, the dehumidifier control can be
used to avoid high humidity and condensation.
To set the dehumidifier parameters:
1. Navigate through the screens:
Uponor > Main menu > Control settings > Cooling >
Dehumidifier control
Example screen:
2. Select Activation
3. Select Enable or Disable
as required and press OK.
4. Select
Dew point margin
5. Set the parameter to the
required value and press
OK.
• Default value: 4°C
• Parameter range: -1°C to +10°C
6. Select Dead zone.
7. Set the parameter to the
required value and press
OK.
• Default value: 2°C
• Parameter range: 1 – 5°C
8. Select Min. run time.
9. Set the parameter to the
required value and press
OK.
• Default value: 30 min
• Parameter range: 5 – 60 min