CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL
28
8.6.3 Min./Max. supply
The parameters Min./Max. supply are used for setting the
minimum and maximum temperatures in the supply circuit.
To set the minimum and maximum supply temperatures:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > Control settings > Cooling >
Min./max. supply
Example screen:
2. Select the required minimum and maximum temperatures.
Minimum supply temperature:
• Default setting: 5 °C
• Setting range: 5–40 °C
• Setting accuracy: 1 °C
Maximum supply temperature:
• Default setting: 25 °C
• Setting range: 5–40 °C
• Setting accuracy: 1 °C
3. Confirm the setting by pressing OK.
8.6.4 Indoor sensor influence
The indoor influence is a supply temperature adjustment that is
depending on the difference of the indoor temperature and the
indoor setpoint. This means that the supply will be increased if
the indoor temperature is to low and it will be decreased if the
indoor temperature is to high. The size of the adjustment is given
by the Indoor sensor influence parameter.
To set the Indoor sensor influence parameter:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > Control settings > Heating >
Indoor sensor influence
Example screen:
2. Select the desired settings.
Lower value:
• Default setting: 4
• Setting range: 0–8
• Setting accuracy: 0.1
Upper value:
• Default setting: 4
• Setting range: 0–8
• Setting accuracy: 0.1
3. Press OK to confirm the setting.
8.6.5 Dew point
To set the dew point parameters:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > Control settings > Cooling >
Dew point
Example screen:
2. Select
Dew point margin
3. Set the parameter to the
required value and press
OK.
• Default setting: 4
• Setting range: 0–8
• Setting accuracy: 1
4. Select Dew point offset
5. Set the parameter to the
required value and press
OK.
• Default setting: 1
• Setting range: -5 to +5
• Setting accuracy: 1
6. Select
Calculated dew point.
The screen displays the
dew point calculated by
the Climate Controller
C-46.
7. Select Sensor mode. This selection is used when one or
more Relative Humidity Sensors H-56 is connected to the
system through the Controller C-56 Radio.
To set the indoor sensor mode parameters:
7.1. Navigate through the screens using the navigation keys:
Uponor > Main menu > Control settings > Cooling
> Sensor mode
Example screen:
7.2. Select Zone.
7.3. Select Mode and press OK.
Default mode: Average
Mode selections: Average, Maximum