52 • vacon description of parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
417 Motor potentiometer DOWN
(2.2.5.8)
Contact closed: Motor potentiometer reference DECREASES until the contact is
opened.
418 Motor potentiometer UP
(2.2.5.9)
Contact closed: Motor potentiometer reference INCREASES until the contact is
opened.
419 Preset speed 1
(2.2.5.5)
420 Preset speed 2
(2.2.5.6)
421 Preset speed 3
(2.2.5.7)
Parameter values are automatically limited between the minimum and maximum
frequencies (parameters ID101 and ID102).
422 AI1/AI2 selection
(2.2.5.17)
With this parameter you can select either AI1 or AI2 signal for frequency reference.
432 Ready
(2.3.3.1)
The frequency converter is ready to operate.
433 Run
(2.3.3.2)
The frequency converter operates (the motor is running).
434 Fault
(2.3.3.3)
A fault trip has occurred.
Default programming: A.1.
435 Inverted fault
(2.3.3.4)
No fault trip has occurred.
436 Warning
(2.3.3.5)
General warning signal.
437 External fault or warning
(2.3.3.6)
Fault or warning depending on par. ID701.
438 Reference fault or warning
(2.3.3.7)
Fault or warning depending on parameter ID700.
439 Overtemperature warning
(2.3.3.8)
The heatsink temperature exceeds +70°C.
440 Reverse
(2.3.3.9)
The Reverse command has been selected.