7.4 Current Transformer Selection
VAMP 24h support phone +358 (0)20 753 3264
Formula to solve needed CT power SN
By replacing the complex power terms with corresponding
resistances in Equation 7.4.1-3 we get,
Equation 7.4.2-2
where the nominal burden resistance is
Winding resistance (See Figure 7.4.1-1)
Wiring resistance (from CT to the relay and back)
Resistance of the protection relay input
Nominal secondary current of the CT
By solving S
N
and substituting k
A
according Equation 7.4.2-2 ,
we get
Equation 7.4.2-3
2
secNCTCTLWCT
NCTALF
NT raSET
N
IRRRR
Ik
IcI
S