Line
ID
Parameter
Name
Range
Default
Setting
Description
619
Event Delay Time
(sec)
1 - 9999 sec 10 sec
XDU pump flow fail 1.Event Enabled DisabledEnabled Enabled
Event: PUMP FLOW
FAIL 1
MESSAGEWARNINGALARM ALARM
620
Event Delay Time
(sec)
1 - 9999 sec 10 sec
XDU pump flow fail 2.Event Enabled DisabledEnabled Enabled
Event: PUMP FLOW
FAIL 2
MESSAGEWARNINGALARM ALARM
621
Event Delay Time
(sec)
1 - 9999 sec 10 sec
XDU fluid flow check filter.Event Enabled DisabledEnabled Enabled
Event: CHECK
WATER SYSTEM
MESSAGEWARNINGALARM WARNING
622
Event Delay Time
(sec)
1 - 9999 sec 10 sec
The current XDU supply fluid temperature is above the threshold.
Event Enabled DisabledEnabled Enabled
Event: HIGH
SUPPLY WATER
TEMP
MESSAGEWARNINGALARM WARNING
623
Event Delay Time
(sec)
1 - 9999 sec 10 sec
The current XDU return fluid temperature is above the threshold.
Event Enabled DisabledEnabled Enabled
Event: HIGH
RETURN WATER
TEMP
MESSAGEWARNINGALARM WARNING
624
Event Delay Time
(sec)
1 - 9999 sec 10 sec
XDU pump operation with no flow.
Event Enabled DisabledEnabled Enabled
Event: PUMP
OPERATION WITH
NO FLOW
MESSAGEWARNINGALARM ALARM
625
Event Delay Time
(sec)
1 - 9999 sec 10 sec
XDU supply fluid sensor failure.
Event Enabled DisabledEnabled Enabled
Event: SUPPLY
FLUID SENSOR
FAILURE
MESSAGEWARNINGALARM ALARM
626
Event Delay Time
(sec)
1 - 9999 sec 10 sec XDU return fluid sensor failure.
Table B.2 Service Menu Alarm Settings by Line ID (continued)
226
Vertiv™ Liebert® iCOM™Installer/User Guide