Line
ID
Parameter
Name
Range
Default
Setting
Description
Event: POWER 4
PHASE LOSS
MESSAGE WARNING ALARM ALARM
S2G4
Phase Loss MB05
shuts unit down
0 = No
1 = Yes
1 (Yes)
Power 5 phase loss.
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Event: POWER 5
PHASE LOSS
MESSAGE WARNING ALARM
ALRM
S2G5
Phase Loss MB06
shuts unit down
0 = No
1 = Yes
1 (Yes)
Power 6 phase loss.
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Event: POWER 6
PHASE LOSS
MESSAGE WARNING ALARM ALARM
S2G6
Event Delay Time
(sec)
10 - 9999 sec 60 sec
Flow sensor fail C1.Event Enabled Disabled Enabled Enabled
Event: FLOW
SENSOR FAIL C1
MESSAGE WARNING ALARM WARNING
S2G7
Event Delay Time
(sec)
10 - 9999 sec 60 sec
Flow sensor fail C2.Event Enabled Disabled Enabled Enabled
Event: FLOW
SENSOR FAIL C2
MESSAGE WARNING ALARM WARNING
S2G8
Event Delay Time
(sec)
10 - 9999 sec 60 sec
TSA sensor fail.Event Enabled Disabled Enabled Enabled
Event: TSA
SENSOR FAIL
MESSAGE WARNING ALARM ALARM
617
Event Delay Time
(sec)
1 - 9999 sec 10 sec
XDU pump inverter fail 1.Event Enabled DisabledEnabled Enabled
Event: PUMP
INVERTER FAIL 1
MESSAGEWARNINGALARM ALARM
618
Event Delay Time
(sec)
1 - 9999 sec 10 sec
XDU pump inverter fail 2.Event Enabled DisabledEnabled Enabled
Event: PUMP
INVERTER FAIL 2
MESSAGEWARNINGALARM ALARM
Table B.2 Service Menu Alarm Settings by Line ID (continued)