Line
ID
Parameter
Name
Range
Default
Setting
Description
S2E8
‒ ‒ ‒
C2 freeze protection.
Event Enabled Disabled Enabled Enabled
Event: C2 FREEZE
PROTECTION
MESSAGE WARNING ALARM ALARM
S2E9
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Damper failure.Event Enabled Disabled Enabled Enabled
Event: DAMPER
FAILURE
MESSAGE WARNING ALARM ALARM
SF2F
‒ ‒ ‒
BMS disconnected.
Event Enabled Disabled Enabled Enabled
Event: BMS
DISCONNECTED
MESSAGE WARNING ALARM WARNING
S2F9
Phase Loss MB01
shuts unit down
0 = No
1 = Yes
1 (Yes)
Power 1 phase loss.
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Event: POWER 1
PHASE LOSS
MESSAGE WARNING ALARM ALARM
S2G1
Phase Loss MB02
shuts unit down
0 = No
1 = Yes
1 (Yes)
Power 2 phase loss.
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Event: POWER 2
PHASE LOSS
MESSAGE WARNING ALARM ALARM
S2G2
Phase Loss MB03
shuts unit down
0 = No
1 = Yes
1 (Yes)
Power 3 phase loss.
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Event: POWER 3
PHASE LOSS
MESSAGE WARNING ALARM ALARM
S2G3
Phase Loss MB04
shuts unit down
0 = No
1 = Yes
1 (Yes)
Power 4 phase loss.Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Table B.2 Service Menu Alarm Settings by Line ID (continued)
224
Vertiv™ Liebert® iCOM™Installer/User Guide