Event: COMP 2A
HIGH TEMP
MESSAGE WARNING ALARM ALARM
S2D8
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2B high temperature.Event Enabled Disabled Enabled Enabled
Event: COMP 2B
HIGH TEMP
MESSAGE WARNING ALARM ALARM
S2D9
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1A short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 1A
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S2E1
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1B short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 1B
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S2E2
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2A short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 2A
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S2E5
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2B short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 2B
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S2E6
Event Delay Time
(sec)
10 - 9999 sec 60 sec
GCB ambient temperature differential.
Event Enabled Disabled Enabled Enabled
Event: GCD
AMBIENT TEMP
DIFF
MESSAGE WARNING ALARM WARNING
S2E7
C1 freeze protection.
Event Enabled Disabled Enabled Enabled
Event: C1 FREEZE
PROTECTION
MESSAGE WARNING ALARM ALARM
Table B.2 Service Menu Alarm Settings by Line ID (continued)
223
Vertiv™ Liebert® iCOM™Installer/User Guide