Vertiv Liebert iCOM - B.2 Service Menu Alarm Settings by Line ID

Vertiv Liebert iCOM
240 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Line
ID
Parameter
Name
Range
Default
Setting
Description
3 SENS FAIL
S2C6
Event Delay Time
(sec)
10 - 9999 sec 120 sec
Static pressure 4 sensor failure.Event Enabled Disabled Enabled Disabled
Event: STAT PRES
4 SENS FAIL
MESSAGE WARNING ALARM ALARM
S2D1
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1A overload.Event Enabled Disabled Enabled Enabled
Event: COMP 1A
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D2
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1B overload.Event Enabled Disabled Enabled Enabled
Event: COMP 1B
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D3
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2A overload.Event Enabled Disabled Enabled Enabled
Event: COMP 2A
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D4
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2B overload.Event Enabled Disabled Enabled Enabled
Event: COMP 2B
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D5
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1A high temperature.Event Enabled Disabled Enabled Enabled
Event: COMP 1A
HIGH TEMP
MESSAGE WARNING ALARM ALARM
S2D6
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1B high temperature.
Event Enabled Disabled Enabled Enabled
Event: COMP 1B
HIGH TEMP
MESSAGE WARNING ALARM
ALARM
S2D7
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2A high temperature.
Event Enabled Disabled Enabled Enabled
Table B.2 Service Menu Alarm Settings by Line ID (continued)
222
Vertiv™ Liebert® iCOM™Installer/User Guide