Line
ID
Parameter
Name
Range
Default
Setting
Description
3 SENS FAIL
S2C6
Event Delay Time
(sec)
10 - 9999 sec 120 sec
Static pressure 4 sensor failure.Event Enabled Disabled Enabled Disabled
Event: STAT PRES
4 SENS FAIL
MESSAGE WARNING ALARM ALARM
S2D1
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1A overload.Event Enabled Disabled Enabled Enabled
Event: COMP 1A
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D2
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1B overload.Event Enabled Disabled Enabled Enabled
Event: COMP 1B
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D3
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2A overload.Event Enabled Disabled Enabled Enabled
Event: COMP 2A
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D4
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2B overload.Event Enabled Disabled Enabled Enabled
Event: COMP 2B
OVERLOAD
MESSAGE WARNING ALARM ALARM
S2D5
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1A high temperature.Event Enabled Disabled Enabled Enabled
Event: COMP 1A
HIGH TEMP
MESSAGE WARNING ALARM ALARM
S2D6
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1B high temperature.
Event Enabled Disabled Enabled Enabled
Event: COMP 1B
HIGH TEMP
MESSAGE WARNING ALARM
ALARM
S2D7
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2A high temperature.
Event Enabled Disabled Enabled Enabled
Table B.2 Service Menu Alarm Settings by Line ID (continued)
222
Vertiv™ Liebert® iCOM™Installer/User Guide