STATIC PRESSURE
S2B7
Event Delay Time
(sec)
10 - 9999 sec 120 sec
High static pressure.Event Enabled Disabled Enabled Disabled
Event: HIGH
STATIC PRESSURE
MESSAGE WARNING ALARM WARNING
S2B8
Event Delay Time
(sec)
10 - 9999 sec 150 sec
Static pressure 1 out of range.Event Enabled Disabled Enabled Disabled
Event: STATPR 1
OUT OF RANGE
MESSAGE WARNING ALARM WARNING
S2B9
Event Delay Time
(sec)
10 - 9999 sec 150 sec
Static pressure 2 out of range.Event Enabled Disabled Enabled Disabled
Event: STATPR 2
OUT OF RANGE
MESSAGE WARNING ALARM WARNING
S2C1
Event Delay Time
(sec)
10 - 9999 sec 150 sec
Static pressure 3 out of range.Event Enabled Disabled Enabled Disabled
Event: STATPR 3
OUT OF RANGE
MESSAGE WARNING ALARM WARNING
S2C2
Event Delay Time
(sec)
10 - 9999 sec 150 sec
Static pressure 4 out of range.Event Enabled Disabled Enabled Disabled
Event: STATPR 4
OUT OF RANGE
MESSAGE WARNING ALARM WARNING
S2C3
Event Delay Time
(sec)
10 - 9999 sec 120 sec
Static pressure 1 sensor failure.Event Enabled Disabled Enabled Disabled
Event: STAT PR 1
SENS FAIL
MESSAGE WARNING ALARM ALARM
S2C4
Event Delay Time
(sec)
10 - 9999 sec 120 sec
Static pressure 2 sensor failure.Event Enabled Disabled Enabled Disabled
Event: STAT PR 2
SENS FAIL
MESSAGE WARNING ALARM ALARM
S2C5
Event Delay Time
(sec)
10 - 9999 sec 120 sec
Static pressure 3 sensor failure.
Event Enabled Disabled Enabled Disabled
Event: STAT PRES
MESSAGE WARNING ALARM ALARM
Table B.2 Service Menu Alarm Settings by Line ID (continued)
221
Vertiv™ Liebert® iCOM™Installer/User Guide