Vertiv Liebert iCOM - Appendix B: Setpoints and Alarm Settings by Line ID; B.1 Line IDs for Setpoint Parameters

Vertiv Liebert iCOM
240 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Line
ID
Parameter
Name
Range
Default
Setting
Description
Event Enabled Disabled Enabled Enabled
Event: HI DEW
POINT SENSOR A
MESSAGE WARNING ALARM WARNING
S2A5
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low dew point sensor A.Event Enabled Disabled Enabled Enabled
Event: LOW DEW
POINT SENSOR A
MESSAGE WARNING ALARM WARNING
S2A6
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High remote sensor.
Event Enabled Disabled Enabled Enabled
MESSAGE WARNING ALARM WARNING
S2A7
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low remote sensor.
Event Enabled Disabled Enabled Enabled
MESSAGE WARNING ALARM WARNING
S2A8
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Power A failure.Event Enabled Disabled Enabled Enabled
Event: POWER A
FAILURE
MESSAGE WARNING ALARM ALARM
S2A9
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Power B failure.Event Enabled Disabled Enabled Enabled
Event: POWER B
FAILURE
MESSAGE WARNING ALARM ALARM
S2B1
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Airflow sensor failure.Event Enabled Disabled Enabled Enabled
Event: AIRFLOW
SENSOR FAIL
MESSAGE WARNING ALARM WARNING
S2B2
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Humidity control sensor failure.Event Enabled Disabled Enabled Enabled
Event: HUM CTRL
SENSOR FAILURE
MESSAGE WARNING ALARM WARNING
S2B6
Event Delay Time
(sec)
10 - 9999 sec 120 sec
Low static pressure.
Event Enabled Disabled Enabled Disabled
Event: LOW
MESSAGE WARNING ALARM WARNING
Table B.2 Service Menu Alarm Settings by Line ID (continued)
220
Vertiv™ Liebert® iCOM™Installer/User Guide

Table of Contents