Line
ID
Parameter
Name
Range
Default
Setting
Description
Event Enabled Disabled Enabled Enabled
Event: HI DEW
POINT SENSOR A
MESSAGE WARNING ALARM WARNING
S2A5
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low dew point sensor A.Event Enabled Disabled Enabled Enabled
Event: LOW DEW
POINT SENSOR A
MESSAGE WARNING ALARM WARNING
S2A6
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High remote sensor.
Event Enabled Disabled Enabled Enabled
‒ MESSAGE WARNING ALARM WARNING
S2A7
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low remote sensor.
Event Enabled Disabled Enabled Enabled
‒ MESSAGE WARNING ALARM WARNING
S2A8
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Power A failure.Event Enabled Disabled Enabled Enabled
Event: POWER A
FAILURE
MESSAGE WARNING ALARM ALARM
S2A9
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Power B failure.Event Enabled Disabled Enabled Enabled
Event: POWER B
FAILURE
MESSAGE WARNING ALARM ALARM
S2B1
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Airflow sensor failure.Event Enabled Disabled Enabled Enabled
Event: AIRFLOW
SENSOR FAIL
MESSAGE WARNING ALARM WARNING
S2B2
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Humidity control sensor failure.Event Enabled Disabled Enabled Enabled
Event: HUM CTRL
SENSOR FAILURE
MESSAGE WARNING ALARM WARNING
S2B6
Event Delay Time
(sec)
10 - 9999 sec 120 sec
Low static pressure.
Event Enabled Disabled Enabled Disabled
Event: LOW
MESSAGE WARNING ALARM WARNING
Table B.2 Service Menu Alarm Settings by Line ID (continued)
220
Vertiv™ Liebert® iCOM™Installer/User Guide