Line
ID
Parameter
Name
Range
Default
Setting
Description
Event Enabled Disabled Enabled Enabled
Event: EC FAN
FAULT
MESSAGE WARNING ALARM ALARM
S294
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High supply temperature.Event Enabled Disabled Enabled Enabled
Event: HI SUPPLY
TEMPERATURE
MESSAGE WARNING ALARM WARNING
S295
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low supply temperature.Event Enabled Disabled Enabled Enabled
Event: LO SUPPLY
TEMPERATURE
MESSAGE WARNING ALARM WARNING
S296
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Reduced eco airflow.Event Enabled Disabled Enabled Enabled
Event: REDUCED
ECO AIRFLOW
MESSAGE WARNING ALARM WARNING
S297
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Eco high temperature override.Event Enabled Disabled Enabled Enabled
Event: ECO HI
TEMP OVERRIDE
MESSAGE WARNING ALARM WARNING
S298
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Temperature control sensor fail.Event Enabled Disabled Enabled Enabled
Event: TEMP CTRL
SENSOR FAIL
MESSAGE WARNING ALARM ALARM
S2A2
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High dew point.Event Enabled Disabled Enabled Enabled
Event: HIGH DEW
POINT
MESSAGE WARNING ALARM WARNING
S2A3
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low dew point.Event Enabled Disabled Enabled Enabled
Event: LOW DEW
POINT
MESSAGE WARNING ALARM WARNING
S2A4
Event Delay Time
(sec)
10 - 9999 sec 30 sec High dew point sensor A.
Table B.2 Service Menu Alarm Settings by Line ID (continued)
219
Vertiv™ Liebert® iCOM™Installer/User Guide