EasyManua.ls Logo

Vertiv Liebert iCOM - A.2 Locations

Vertiv Liebert iCOM
240 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Line
ID
Parameter
Name
Range
Default
Setting
Description
S27C Edit Cust Input 2
(20 digits)
0-9
A-Z
a-z
&* / . + - _ : @ \
CUSTOMER
INPUT 2
Edit customer input 2 text,
S27D Edit Cust Input 3
(20 digits)
0-9
A-Z
a-z
&* / . + - _ : @ \
CUSTOMER
INPUT 3
Edit customer input 3 text
S27E Edit Cust Input 4
(20 digits)
0-9
A-Z
a-z
&* / . + - _ : @ \
CUSTOMER
INPUT 4
Edit customer input 4 text.
S288
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1 short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 1
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S289
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2 short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 2
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S290
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Emergency power.
Event Enabled Disabled Enabled Enabled
Event:
EMERGENCY
POWER
MESSAGE WARNING ALARM WARNING
S291
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Condenser 1 failure.
Event Enabled Disabled Enabled Enabled
Event:
CONDENSER 1
FAILURE
MESSAGE WARNING ALARM WARNING
S292
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Condenser 2 failure.
Event Enabled Disabled Enabled Enabled
Event:
CONDENSER 2
FAILURE
MESSAGE WARNING ALARM WARNING
S293
Event Delay Time
(sec)
10 - 9999 sec 15 sec EC fan fault.
Table B.2 Service Menu Alarm Settings by Line ID (continued)
218
Vertiv™ Liebert® iCOM™Installer/User Guide

Table of Contents

Other manuals for Vertiv Liebert iCOM

Related product manuals