Line
ID
Parameter
Name
Range
Default
Setting
Description
S27C Edit Cust Input 2
(20 digits)
0-9
A-Z
a-z
&* / . + - _ : @ \
CUSTOMER
INPUT 2
Edit customer input 2 text,
S27D Edit Cust Input 3
(20 digits)
0-9
A-Z
a-z
&* / . + - _ : @ \
CUSTOMER
INPUT 3
Edit customer input 3 text
S27E Edit Cust Input 4
(20 digits)
0-9
A-Z
a-z
&* / . + - _ : @ \
CUSTOMER
INPUT 4
Edit customer input 4 text.
S288
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 1 short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 1
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S289
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Compressor 2 short cycle.Event Enabled Disabled Enabled Enabled
Event: COMP 2
SHORT CYCLE
MESSAGE WARNING ALARM WARNING
S290
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Emergency power.
Event Enabled Disabled Enabled Enabled
Event:
EMERGENCY
POWER
MESSAGE WARNING ALARM WARNING
S291
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Condenser 1 failure.
Event Enabled Disabled Enabled Enabled
Event:
CONDENSER 1
FAILURE
MESSAGE WARNING ALARM WARNING
S292
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Condenser 2 failure.
Event Enabled Disabled Enabled Enabled
Event:
CONDENSER 2
FAILURE
MESSAGE WARNING ALARM WARNING
S293
Event Delay Time
(sec)
10 - 9999 sec 15 sec EC fan fault.
Table B.2 Service Menu Alarm Settings by Line ID (continued)
218