Parameter
Name
Range
Default
Setting
Description
Event: HIGH
TEMPERATURE
MESSAGE WARNING ALARM ALARM
S281
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Loss of Air Blower 1.Event Enabled Disabled Enabled Disabled
Event: LOSS OF AIR
BLOWER 1
MESSAGE WARNING ALARM ALARM
S282
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Reheat LockoutEvent Enabled Disabled Enabled Enabled
Event: REHEAT
LOCKOUT
MESSAGE WARNING ALARM WARNING
S283
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Humidifier lockout.Event Enabled Disabled Enabled Enabled
Event: HUMIDIFIER
LOCKOUT
MESSAGE WARNING ALARM WARNING
S284
Event Delay Time
(sec)
10 - 9999 sec 10 sec
FC lockout.Event Enabled Disabled Enabled Enabled
Event: FC
LOCKOUT
MESSAGE WARNING ALARM WARNING
S285
Compressor
Lockout Option
0 = ALL
1 = 1 (A)
2 = 2 (A)
3 = 1B
4 = 2B
5 = 1A + 2A
6 = 1B + 2B
7 = 1A + 1B
8 = 2A + 2B
0(ALL)
Compressor(s) lockout.
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabed
Disabled Enabled Enabled
Event:
COMPRESSOR
(S) LOCKOUT
MESSAGE WARNING ALARM
WARNING
S27B Edit Cust Input 1
(20 digits)
0-9
A-Z
a-z
&* / . + - _ : @ \
CUSTOMER
INPUT 1
Edit customer input 1 text.