Line
ID
Parameter
Name
Range
Default
Setting
Description
UNIT1
S271
Event Delay Time
(sec)
Unit X disconnected.Event Enabled Disabled Enabled Enabled
Event: UNIT 01
DISCONNECTED
MESSAGE WARNING ALARM WARNING
S272
Event: Loss of
power Autoreset
Delay
60 - 3600 sec 300 sec
Loss of power.
Event Enabled Disabled Enabled Enabled
Event: LOSS OF
POWER
MESSAGE WARNING ALARM WARNING
S275
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Customer input 1.Event Enabled Disabled Enabled Enabled
Event: CUSTOMER
INPUT 1
MESSAGE WARNING ALARM ALARM
S276
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Customer input 2.Event Enabled Disabled Enabled Enabled
Event: CUSTOMER
INPUT 2
MESSAGE WARNING ALARM ALARM
S277
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Customer input 3.Event Enabled Disabled Enabled Enabled
Event: CUSTOMER
INPUT 3
MESSAGE WARNING ALARM ALARM
S278
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Customer input 4.Event Enabled Disabled Enabled Enabled
Event: CUSTOMER
INPUT 4
MESSAGE WARNING ALARM ALARM
S279
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Call service.Event Enabled Disabled Enabled Enabled
Event: CALL
SERVICE
MESSAGE WARNING ALARM ALARM
S280
Event Delay Time
(sec)
10 - 9999 sec
10 sec
High temperature.
Event Enabled Disabled Enabled Enabled
Table B.2 Service Menu Alarm Settings by Line ID (continued)