Line
ID
Parameter
Name
Range
Default
Setting
Description
Event Enabled Disabled Enabled Enabled
Event: SMOKE
DETECTED
MESSAGE WARNING ALARM ALARM
S264
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Water under floor.Event Enabled Disabled Enabled Enabled
Event: WATER
UNDER FLOOR
MESSAGE WARNING ALARM ALARM
S265
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Cond. pump high water.
Event Enabled Disabled Enabled Enabled
Event: COND
PUMP-HIGH
WATER
MESSAGE WARNING ALARM ALARM
S266
Event Delay Time
(sec)
0 = AR
1 = MR
0 (AR)
Loss of flow. AR = Auto Reset, MR = Manual Reset.
Event Enabled 10 - 9999 sec 10 sec
Event Number 107
Enabled
Disabled Enabled Enabled
Event: LOSS OF
FLOW
MESSAGE WARNING ALARM ALARM
S267
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Standby glycol pump ON.Event Enabled Disabled Enabled Enabled
Event: STANDBY
GLYCOL PUMP ON
MESSAGE WARNING ALARM ALARM
S268
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Standby unit ON.Event Enabled Disabled Enabled Enabled
Event: STANDBY
UNIT ON
MESSAGE WARNING ALARM ALARM
S269
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Humidifier problem.Event Enabled Disabled Enabled Enabled
Event: HUMIDIFIER
PROBLEM
MESSAGE WARNING ALARM ALARM
S270
Event Delay Time
(sec)
10 - 9999 sec 300 sec
No connection with Unit 1.
Event Enabled Disabled Enabled Enabled
Event: NO
CONNECTION W/
MESSAGE WARNING ALARM WARNING
Table B.2 Service Menu Alarm Settings by Line ID (continued)
215
Vertiv™ Liebert® iCOM™Installer/User Guide