Vertiv Liebert iCOM - 13.6.5 Wiring Cooling Units with Wall Mount Displays

Vertiv Liebert iCOM
240 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Line
ID
Parameter
Name
Range
Default
Setting
Description
Event Enabled Disabled Enabled Enabled
Event: SMOKE
DETECTED
MESSAGE WARNING ALARM ALARM
S264
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Water under floor.Event Enabled Disabled Enabled Enabled
Event: WATER
UNDER FLOOR
MESSAGE WARNING ALARM ALARM
S265
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Cond. pump high water.
Event Enabled Disabled Enabled Enabled
Event: COND
PUMP-HIGH
WATER
MESSAGE WARNING ALARM ALARM
S266
Event Delay Time
(sec)
0 = AR
1 = MR
0 (AR)
Loss of flow. AR = Auto Reset, MR = Manual Reset.
Event Enabled 10 - 9999 sec 10 sec
Event Number 107
Enabled
Disabled Enabled Enabled
Event: LOSS OF
FLOW
MESSAGE WARNING ALARM ALARM
S267
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Standby glycol pump ON.Event Enabled Disabled Enabled Enabled
Event: STANDBY
GLYCOL PUMP ON
MESSAGE WARNING ALARM ALARM
S268
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Standby unit ON.Event Enabled Disabled Enabled Enabled
Event: STANDBY
UNIT ON
MESSAGE WARNING ALARM ALARM
S269
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Humidifier problem.Event Enabled Disabled Enabled Enabled
Event: HUMIDIFIER
PROBLEM
MESSAGE WARNING ALARM ALARM
S270
Event Delay Time
(sec)
10 - 9999 sec 300 sec
No connection with Unit 1.
Event Enabled Disabled Enabled Enabled
Event: NO
CONNECTION W/
MESSAGE WARNING ALARM WARNING
Table B.2 Service Menu Alarm Settings by Line ID (continued)
215
Vertiv™ Liebert® iCOM™Installer/User Guide